Instruksjon for lav temperatur bruk
Når enhetens minimum temperatur (18 C) er oppnådd, vil MovinCool generer sin egen varme til å begynne sin avfuktnings prosess.
Beregning

Example calculation
Measured Intake temp = 26 º C Measured Rh = 64%
Measured outlet temp = 14 º C Measured Rh = 89%
Measured airflow volume = 3300 m3/h
Formula is E.ø/ v
E = enthalpy
ø = airflow volume
v = specific volume of air
Enthalpy = 14.4 - 9 = 5.4
Specific volume = 0.827
5.4 x 3300 / 0.827 = 21547.76 Kcal/hr
21547.76 / 860 = 25.05 Kwatt
Dehumidification
(Red dotted lines)
Absolute humidity 0.0138 - 0.009 = 0.0048
0.0048x3300 = 15.84 kg/h or 15.84 liters/h
|